JAGUAR VXS
Sensorless Vector Variable Frequency Inverters 0.4kW to 4.0kW s High performance Torque Vector Control s Over 200% torque at 1 Hz s Footprint filters for EMC compliance s User friendly auto tuning s Ultra compact IP40 enclosure s Fast torque response s Low motor noise profile s User programmable I/O s Integral detachable keypad s Single and three phase versions s RS485 communications port (optional) s Renowned IMO 5 year warranty
Compact Single and Three Phase Torque Vector Systems for Small Three Phase Motors
5
Three Phase Input VXS220-1 2.2 11.0 20.0 VXS40-3 0.37 0.55 1.6 1.3 VXS75-3 0.75 2.5 2.2 VXS150-3 1.5 3.7 4.3 VXS220-3 VXS400-3 2.2 5.5 6.0 4.0 9.0 9.8 VXS150-1 1.5 8.0 14.0
Electrical specifications
Single Phase Input Jaguar VXS order codes Motor rating (kW) Maximum rated O/P current (A) 100% Rated I/P current ARMS Input voltage Input frequency Output voltage Output frequency
PRICE INFORMATION AND ORDERING
VXS20-1 0.2 1.5 2.95
VXS40-1 0.37 0.55 3.0 4.1
VXS75-1 0.75 5.0 7.2
200 - 240 AC, ±10%, 1 phase 50 - 60 Hz, ±5%
380 - 480 AC, +10 to -15%, 3 phase
AC, 0 - VINPUT PWM 0.2 - 400 Hz
General specifications
Heat loss at minimum car rier frequency (W) Weight (Kg) Enclosure rating Cooling method Ambient temperature Relative humidity V ibration Altitude Natural Convection Fan Assisted 23 1.1 45 1.6 56 1.7 81 2.7 129 2.8 IP40 Natural Convection Fan Assisted 42 1.8 51 1.8 67 2.7 97 2.7 120 3.2
-10 to +50°C (remove covers >+40°C) 20 to 95% non condensing 5.9 m/s2 (0.6G) max 1000 metres max
Jaguar VXS Connection diagram
WARNING! This equipment must be earthed CAUTION: Do not short circuit. Terminal P24 to terminal 11, CM or CME
F
240V 1Ø or 415V 3Ø 50/60 Hz
C
L1
PANEL CONTROL
U
PRG MODE Hz A r/min m/min RUN V
F F
NOTE: Figures in brackets are for single phase models
L2 (L) L3 (N)
V
RUN STOP
PRG RESET
M
PRICE INFORMATION AND ORDERING
FUNC DATA
W
Frequency reference current input (4~20 mA DC) Manual frequency setting potentiometer (10K/1W)
(+) ()
C1 13 12 11
G GND(PE) (PE
DC REACTOR (OPTIONAL) LINK
P1 (+)
EXTERNAL BRAKE RESISTOR (OPTIONAL)
DB
+24V Forward operation and stop command Reverse operation and stop command Coast - to - stop command Alarm reset
P24 FWD REV BX 30C RST X1 FMP 30A 30B
From P24* terminal From THR terminal Alarm output (any fault) (Relay shown in power ON or OFF and healthy state)
PULSE
Multistep frequency select
X2 X3 FMA
Digital frequency meter
To CM terminal Analog frequency meter (10 V/1 mA DC)
Function extension input
X4 CM
To terminal 11
External alarm input
THR
YIE CMC
Programmable output Common for YIE
*
NOTE: Under no circumstances should the above guide be considered sufficient for the attainment of relevant EMC emission limits. Please consult the product manual for full information regarding compliance.
Power Terminals
Symbol L1, L2, L3 L, N U, V, W P1, (+) (+), DB GND (PE) Terminal Name Main input power terminals Main input power terminals Power output terminals DC reactor terminals Exter nal brake resistor terminals Ear th terminal Description For connecting 3 phase power supply (VXS - 3 only) For connecting single phase power supply (VXS - 1 only) For 3 phase AC induction motor Optional DC reactor terminals for improving power factor (fitted with shorting link) Connection for brake resistor to increase braking torque Safety electrical earth
Jaguar VXS Control circuit terminals
Purpose Terminal Terminal Name Speed reference 0V common Reference input Potentiometer supply Cur rent loop input For ward and stop command Reverse and stop command Coast - to - Stop command Exter nal trip or Control Inputs RST Enable/disable data edit mode Trip/Alarm reset Description
11 Analog Frequency Setting 12 13 C1 FWD
For use with terminals 12, 13, C1 and FMA 0 - 10V DC input, impedance = 22 K +10V DC power supply for 1 K speed control potentiometer. Output 10mA max. 4 - 20mA input, impedance = 250 FWD - P24 Closed Motor runs forward Open Motor stops REV - P24 Closed Motor runs in reverse Open Motor stops If both FWD and REV are opened or closed, then the inverter output stops
REV
BX THR
BX - P24 Closed Output inhibited instantaneously Open Normal · THR - P24 Closed Normal Open Trips output instantaneously or · THR - P24 Closed Normal Open Data protected If RST - P24 is closed for 100mS following a trip condition, the inverter will reset Combinations of X1, X2, X3 - P24 will call for preset frequencies to be output Depending upon the setting of function No. 43 terminal acts as Acc 2 / Dec 2 pattern select Extension to 15 preset speeds 2nd motor V/F profile FWD/REV latch for 3-wire I/P Inter nal 24V DC supply for control inputs Common terminal for FMP and digital inputs Output frequency, current, torque or load factor can be selected, 0 - 10V DC, 1mA maximum Up to 2 metres of cable is recommended for connection to this terminal Output proportional to frequency of motor 6 kHz maximum, fully scalable Selectable for:1) Inverter running 2) Frequency level detected 3) Frequency hysteresis band reached 4) Undervoltage trip 5) Torque limiting 6) Auto Restart Maximum 27V DC, 50 mA Used for YIE output only Normally 30B - 30C closed with power OFF or ON, with drive output healthy 30A - 30C closes on fault. Rated 250V, 0.3A
X1, X2, X3 X4
Preset speeds Function extension
P24 CM FMA Meter Outputs FMP YIE
+24V DC supply Common terminal Analogue output
Digital output Programmable output
Control Outputs
CMC 30A 30B 30C
Common terminal
Fault relay
|
|