Details, datasheet, quote on part number:D53TP50D-10
| |
Datasheet text preview:
Series 53TP
25-50Amp · 240/480 Vac · 3 PHASE
· SCR Output · LED Status Indicator · Prot ect ive Cover Available (Part No. KS300) · Panel M ount
Three-phase solid state relays switch up to 530 Vrms directly to loads such as motors, transformers, heating elements, etc. Available with either AC or DC input (coil) control in zero-voltage or random turn-on switching versions. Manufactured in Crydom's ISO 9001 Certified facility for optimum product performance and reliability.
· Int egrat ed Overvoltage Prot ect ion by Automatic Self Turn-On (Suff ix P)
MODEL NUMBERS
D53TP25D
D53TP50D
A53TP25D
A53TP50D
O U T P U T SPECIFICATIONS
Operating Voltage (47-63 Hz) [Vrms] Load Current Range [Arms] Transient Overvoltage [Vpk] Max. Surge Current, (16.6ms) [Apk] Max. On-State Voltage Drop @ Rated Current [Vpk] Thermal Resistance Junction to Case (RJC) [°C/W] Maximum I2 t for Fusing, (8.3 msec.) [A2sec] Max. Off-State Leakage Current @ Rated Voltage [mArms] Min. Off-State dv/dt @ Max. Rated Voltage [V/”sec] Max. Turn-On Time Max. Turn-Off Time Power Factor (Min.) with Max. Load
48-530 .05-25 1200 250 1.6 1.02 260 10 500 1/2 Cycle 1/2 Cycle 0.5
48-530 .05-50 1200 625 1.6 .63 1620 10 500 1/2 Cycle 1/2 Cycle 0.5
48-530 .05-25 1200 250 1.6 1.02 260 10 500 10.0 msec 40.0 msec 0.5
48-530 .05-50 1200 625 1.6 .63 1620 10 500 10.0 msec 40.0 msec 0.5
I N P U T SPECIFICATIONS
Control Voltage Range Max. Turn-On Voltage Min. Turn-Off Voltage Nominal Input Impedance Typical Input Current
D C CONTROL
3-32 Vdc 3.0 Vdc 1.0 Vdc 450 Ohms 10mA @ 5 Vdc
A C CONTROL
90-280 Vrms (60Hz) 90 Vrms 10 Vrms 54.8k Ohms 2.2mA @ 120 Vrms, 4.4mA @ 240 Vrms
G E N E R A L NOTES
©2001 CRYDOM CORP, Specifications subject to change without notice.
All parameters at 25șC and per section unless otherwise specified. Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1 Heat sinking required, for derating curves see page 2. Turn-on time for random turn-on versions is 0.02 msec (DC Control Models).
FastFax Document No.161 SERIES53TP. REV. 011602 PAGE 1 OF 2
For recommended applications and more information contact: USA: Sales Support (877) 502-5500 Tech Support (877) 702-7700 FAX (619) 710-8540 Crydom Corp, 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154 Email: sales@crydom.com WEB SITE: http://www.crydom.com UK: +44 (0)1202 365070 · FAX +44 (0)1202 365090 Crydom International Ltd., 7 Cobham Road, Ferndown Industrial Estate, Ferndown, Dorset BH21 7PE, Email: intsales@crydom.com. GERMANY: +49 (0)180 3000 506
Series 53TP
25-50Amp · 240/480 Vac · 3 PHASE
G E N E R A L SPECIFICATIONS
Dielectric Strength 50/60Hz Input/Output/Base Insulation Resistance (Min.) @ 500 Vdc Max. Capacitance Input/Output Ambient Operating Temperature Range Ambient Storage Temperature Range
M E C H A N I C A L SPECIFICATIONS Weight: (typical)
4000 Vrms 109 Ohm 8 pF -40 to 80șC -40 to 125șC
10.3 oz. (315g) Thermally Conductive Epoxy Screws and Saddle Clamps Furnished
Encapsulation: Terminals:
A V A I L A B L E OPTIONS -10 Non-Zero Cross, Instantaneous Turn-On Example: D53TP50D-10 10-32 TERMINAL DP 2 Controlled, 1 Linked (A1-A2) (6 PLACES ) Example: D53DP50D P Internal Overvoltage Protection. Relay Will Self Trigger Between 900-1200 Vpk. Not Suitable For 2.125 1.875 (47.6) Capacitive Loads. (54.0) Agencies Approval Pending. Example: D53TP50DP
4.09 (103.8)
0.21 (5.3)
1.18 (30.0)
A1
B1
C1
INPUT STATUS LED
+
INPUT
2.89 (73.4) 0.79 (20.1)
All dimensions are in inches (millimeters)
Screw Torque Requirements: 6-32 Screws - 10 in. lbs., 8-32 and 10-32 Screws - 20in. lbs. (Screws dry without grease.)
SOLID-STATE RELAY
A2
B2
C2
--
Crydom Heat Sinks offer excellent thermal management and are per fectly matched to the load current ratings of Crydom panel mount relays. Request Crydom's Heat Sink specification sheet for all the details.
.39 REF (10.0)
1.56 (39.6) 3.62 (91.9)
.78 (19.8) 1.36 (34.5)
6-32 TERMINAL (2 PLACES )
.79 (20.1) .94 (24.0)
.125 (3.2) BASE PLATE THICKNESS
C U R R E N T DERATING CURVES
60
Power Dissipation
A53DP25D, D53DP25D .5șC/W
1șC/W
Base Plate Temp [șC] Power Dissipation
A53TP25D, D53TP25D
80 100
1șC/W
Base Plate Temp [șC] Base Plate Temp [șC]
1.5șC/W
100 105 110
60 40
0.5șC/W
40
105 110 115 120
1.5șC/W
20
115 120
20
0 5 10 15 20 25 20 40 60 80
Load Current [Arms] Max Ambient Temp. [șC]
0 5 10 15 20 25 20 40 60 80
Load Current [Arms] Max Ambient Temp. [șC]
A53DP50D, D53DP50D
120
0.25șC/W
Power Dissipation
A53TP50D, D53TP50D
180 90
Base Plate Temp [șC] Power Dissipation
90
.25șC/W .5șC/W
90
0.5șC/W 1șC/W
95 100 105 110
150 120 90
95 100 105
60 30
1.5șC/W
1șC/W
110 115 120
60 30 0
115 120
1.5șC/W
0
10
20
30
40
50
20
40
60
80
10
20
30
40
50
20
40
60
80
Load Current [Arms]
Max Ambient Temp. [șC]
Load Current [Arms]
Max Ambient Temp. [șC]
APPROVALS UL E116950 CSA LR81689 VDE 5941 UG
FastFax Document No.161 SERIES53TP Rev. 011602 PAGE 2 OF 2
©2001 CRYDOM CORP, Specifications subject to change without notice.
For recommended applications and more information contact: USA: Sales Support (877) 502-5500 Tech Support (877) 702-7700 FAX (619) 710-8540 Crydom Corp, 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154 Email: sales@crydom.com WEB SITE: http://www.crydom.com UK: +44 (0)1202 365070 · FAX +44 (0)1202 365090 Crydom International Ltd., 7 Cobham Road, Ferndown Industrial Estate, Ferndown, Dorset BH21 7PE, Email: intsales@crydom.com. GERMANY: +49 (0)180 3000 506
|
|