Details, datasheet, quote on part number:G3PB-jjjB-3N-VD
| |
Datasheet text preview:
Industrial 3 -- Phase Solid State Relay
H A comprehensive lineup that now includes H H H H H H
480-VAC models Used to switch electrical loads including Omron's temperature coltrollers No audible noise; EMI (Electro-Magnetic Interference) and vibration resistant Improved heat sink increases life and reliability Voltage turn-on at zero crossing reduces initial inrush load currents LED indicator turns on when control power is applied DIN rail or panel mountable
G3PB
Ordering Information
Input operating voltage (Rated voltage) 9.6 to 30 VDC (12 to 24 VDC) Operating load voltage (Rated load voltage) 75 to 264 VAC (100 to 240 VAC) Max. inrush current (60Hz, 1 cycle) 150A 220A 440A Max. load current 15 amps 25 amps 35 amps 45 amps 180 to 528 VAC (200 to 480 VAC) 220A 15 amps 25 amps 440A 35 amps 45 amps Part number G3PB -215B -3N -VD DC12 - 24V G3PB -215B -2N -VD DC12 - 24V G3PB -225B -3N -VD DC12 - 24V G3PB -225B -2N -VD DC12 - 24V G3PB -235B -3N -VD DC12 - 24V G3PB -235B -2N -VD DC12 - 24V G3PB -245B -3N -VD DC12 - 24V G3PB -245B -2N -VD DC12 - 24V G3PB -515B -3N -VD DC12 - 24V G3PB -515B -2N -VD DC12 - 24V G3PB -525B -3N -VD DC12 - 24V G3PB -525B -2N -VD DC12 - 24V G3PB -535B -3N -VD DC12 - 24V G3PB -535B -2N -VD DC12 - 24V G3PB -545B -3N -VD DC12 - 24V G3PB -545B -2N -VD DC12 - 24V Note: 1. All models have zero cross function. 2. Number of poles indicated by - 2N (for two poles) or - 3N (for three poles) in part number. -
J Accessories
DIN Rail Mounting Track
Description DIN rail track, 7.3 mm (0.29 in) depth; 50 cm (1.64 ft) length DIN rail track, 7.3 mm (0.29 in) depth; 1 m (3.28 ft) length End plate Spacer Part number PFP-50N PFP-100N PFP-M PFP-S
1
G3PB
G3PB
Application Example
Temperature Controller SSR
Load Heater Voltage output terminal (for driving SSR)
Input
Output
Power supply for l oad
Direct connection possible
Omron's SSRs offer these advantages over electro-mechanical relays (EMRs):
D D D Longer service life with no contacts to wear out Reduced electromagnetic interference Faster response time D D D Vibration and shock resistance No audible noise when switching Enhanced reliability
Specifications
J Ratings (at an Ambient Temperature of 25°C)
Operating Circuit (Common)
Item Rated operating voltage Operating voltage range Rated input current (Impedance) Must-operate voltage Reset voltage Insulation method Operation indicator Common 12 to 24 VDC 9.6 to 30 VDC 10 mA max. (at 24 VDC) 9.6 VDC max. 1 VDC min. Phototriac coupler Yellow LED
Output
Item G3PB215B3N-VD G3PB215B2N-VD G3PB225B3N-VD G3PB225B2N-VD G3PB235B3N-VD G3PB235B2N-VD G3PB245B3N-VD G3PB245B2N-VD
Rated voltage Operating voltage range Rated carry current (see note) Minimum load current Inrush current resistance (peak value) Permissible I2t (half 60-Hz wave) Item
100 to 240 VAC 75 to 264 VAC 15 A 0.2 A 150 A (60 Hz, 1 cycle) 121 A2s G3PB515B3N-VD G3PB515B2N-VD 220 A (60 Hz, 1 cycle) 260 A2s G3PB525B3N-VD G3PB525B2N-VD 25 A 35 A 0.5 A 440 A (60 Hz, 1 cycle) 1,260 A2s G3PB535B3N-VD G3PB535B2N-VD G3PB545B3N-VD G3PB545B2N-VD 45 A
Rated voltage Operating voltage range Rated carry current (see note) Minimum load current Inrush current resistance (peak value) Permissible I2t (half 60-Hz wave)
200 to 480 VAC 180 to 528 VAC 15 A 0.5 A 220 A (60 Hz, 1 cycle) 260 A2s 440 A (60 Hz, 1 cycle) 1,260 A2s 25 A 35 A 45 A
2
G3PB
Note:
G3PB
Rated carry current varies depending on the ambient temperature. For details, refer to Load Current vs. Ambient Temperature in Engineering Data.
J Characteristics
Item G3PB215B3N-VD G3PB215B2N-VD G3PB225B3N-VD G3PB225B2N-VD G3PB235B3N-VD G3PB235B2N-VD G3PB245B3N-VD G3PB245B2N-VD
Operate time Release time Output ON voltage drop Leakage current (see note) Insulation resistance Dielectric strength Vibration resistance Shock resistance Ambient temperature Ambient humidity Weight Approved standards EMC
1/2 of load power source cycle + 1 ms max. (DC input) 1/2 of load power source cycle + 1 ms max. (DC input) 1.6 V (RMS) max. 10 mA (at 200 VAC) 100 M min. (at 500 VDC) 2,500 VAC, 50/60 Hz for 1 min 10 to 55 Hz, 0.175-mm single amplitude 294 m/s2 (98 m/s2 with reverse mounting) Operating: Storage: - 30°C to 80°C ( - 22°F to 176°F) with no icing or condensation - 30°C to 100°C ( - 30°F to 2121°F) with no icing or condensation Approx. 1.45 kg (3.20 lbs) Approx. 1.65 kg (3.64 lbs) Approx. 2.0 kg (4.41 lbs)
Operating: 45% to 85% Approx. 1.25 kg (2.75 lbs) UL508, CSA22.2 No. 14, EN60947-4-3 (IEC947-4-3) approved by VDE (From April 2001) Emission Immunity Immunity Immunity Immunity Immunity Immunity ESD Electromagnetic EFT Surge transient RF disturbance Dips EN55011 Group 1 Class B IEC947-4-3, EN61000-4-2 4 kV contact discharge 8 kV air discharge IEC947-4-3, EN61000-4-3 10 V/m (80 MHz to 1 GHz) IEC947-4-3, EN61000-4-4 2 kV AC power-signal line IEC947-4-3, EN61000-4-5 Normal mode ±1 kV, Common mode ±2 kV IEC947-4-3, EN61000-4-6 10 V (0.15 to 80 MHz) IEC947-4-3, EN61000-4-11
Note:
The leakage current of phase S will be approximately 3 times larger if the 2-element model is applied.
3
|
|