Part: 0KLQ005.T

Category:
 Discrete
   -> Diodes & Rectifiers
     -> Protection

Description: Supplementary Overcurrent Protection

Company: Littelfuse

Datasheet: Download 0KLQ005.T datasheet     File size : 195 kB

Request For quote: Find where to buy 0KLQ005.T



Datasheet text preview:
Midget Fuses
Supplementary Overcurrent Protection KLK Fuses
FAST-ACTING s 600 VAC
Fast-acting, high-interrupting capacity, current-limiting type fuse. Especially suited for control circuits, street lighting, H.I.D. lighting, computers, and other applications without high inrush currents. Voltage Rating: 600 Volts AC 500 Volts DC Interrupting Rating: UL Listed 100,000 amperes rms symmetrical (Capable of 200,000 amperes) Ampere Ratings: /10 /8 2 /10 1 /4 3 /10 1 /2 3 /4 Approvals:
1 1

1 11/2 2 21/2 3 31/2

4 5 6 7 8 9

10 12 15 20 25 30

Standard 248-14 UL Listed 3/10-30A (File No: E10480) CSA Certified 3/10-30A (File No: LR29862) Versions available to meet MIL-F-5160/60, QPL F60C: Contact Factory. Dimensions: 13/32" x 1-1/2"
Example part number (series & amperage): KLK 1-1/2

KLKD Fuses
FAST-ACTING s 600 VAC/DC
Fast-acting, high-interrupting capacity, current-limiting type fuse. Especially suited for DC control circuits, street lighting, H.I.D. lighting, computers, and other applications. Voltage Rating: 600 Volts AC/DC Interrupting Rating: AC: 100,000 amperes rms symmetrical; DC: 10,000 amperes

Ampere Ratings: 1 /10 1 4 10 1 /8 11/2 5 12 2 /10 2 6 15 1 /4 21/2 7 20 3 /10 3 8 25 1 /2 31/2 9 30 3 /4 Approvals: Standard 248-14 UL Listed 3/10-30A (File No: E10480) CSA Certified 3/10-30A (File No: LR29862) Dimensions: 13/32" x 1-1/2"
Example part number (series & amperage): KLKD 30

FLM Fuses
TIME-DELAY s 250 VAC
Use FLM 250 volt time-delay fuses to protect control circuit transformers, solenoids, and other circuits with high inrush currents. Excellent for supplemental protection of small motors. For motor branch-circuit protection, See Class CC fuses. Voltage Rating: 250 Volts AC Interrupting Rating: AC: 10,000 amperes rms symmetrical.

Ampere Ratings: 1 /10 11/8 3 7 15 /100 11/4 32/10 8 2 4 1 /10 1 /10 3 /2 9 1 /4 11/2 4 10 3 /10 16/10 41/2 12 4 /10 18/10 5 15 1 6 /2 2 5 /10 20 6 /10 21/4 6 25 8 /10 21/2 61/4 30 1 28/10 Approvals: Standard 248-14 UL Listed (File No: E10480) CSA Certified (File No: LR29862) Dimensions: 13/32" x 1-1/2"
Example part number (series & amperage): FLM 15

FLQ Fuses
TIME-DELAY s 500 VAC
These 500 volt time-delay fuses provide excellent supplemental protection of control power transformers, solenoids, and circuits with high inrush currents. UL and CSA 500 volt ratings permit use on 480 volt circuits. FLQ fuses also provide supplemental protection to small motors. For motor branch-circuit protection, see Class CC fuses. Voltage Rating: 500 Volts AC Interrupting Rating: 10,000 amperes rms symmetrical

Ampere Ratings: 1 8 /10 /10 32/10 8 1 /8 1 31/2 9 15 1 /100 1 /8 4 10 3 /16 11/4 41/2 12 2 /10 11/2 5 14 1 /4 16/10 56/10 15 3 /10 2 6 20 4 /10 21/4 61/4 25 1 /2 21/2 7 30 6 /10 3 Approvals: Standard 248-14 UL Listed (File No: E10480) CSA Certified (File No: LR29862) Dimensions: 13/32" x 1-1/2"
Example part number (series & amperage): FLQ 1/2

RECOMMENDED FUSE BLOCKS
L60030M series. Refer to Fuse Block section of this catalog for additional information.

49

Midget Fuses
Supplementary Overcurrent Protection BLN Fuses
FAST-ACTING s 250 VAC
Fiber tube, 250 volt BLN fuses provide lowcost protection for military applications and control circuits. Voltage Rating: 250 Volts AC Interrupting Rating: 10,000 amperes rms symmetrical Ampere Ratings: 1 2 3 4 5 6 8 10 12 15 20 25 30

Approvals: Standard 248-14 UL Listed (File No: E10480) CSA Certified (File No: LR29862) Versions available to meet MIL-F-15160/9, QPL F09A: Contact Factory Dimensions: 13/32" x 1-1/2"
Example part number (series & amperage): BLN 30

BLF Fuses
FAST-ACTING s 125/250 VAC
Laminated tube BLF fuses are the lowest price midget fuse. They are suitable for control circuit and instrument protection in dry locations. Voltage Ratings: 250 Volts AC: 1/2 ­ 15 amperes; 125 Volts AC: 20 ­ 30 amperes Interrupting Rating: 10,000 amperes rms symmetrical

Ampere Ratings: /2 1 11/2 2 21/2
1

3 4 5 6 61/4

7 8 9 10 12

15 20 25 30

Approvals: Standard 248-14 UL Listed (File No: E10480) CSA Certified (File No: LR29862) Dimensions: 13/32" x 1-1/2"
Example part number (series & amperage): BLF 5

BLS Fuses
FAST-ACTING s 250/600 VAC
BLS fuses are 1-3/8" long in contrast to other midget fuses which are 1-1/2". They provide space-saving, low-cost, protection to street lighting, metering, control and electronic circuits. Voltage Rating: 600 Volts AC: 2/10 ­ 5 amperes; 250 Volts AC: 6 ­ 10 amperes Interrupting Rating: 10,000 amperes rms symmetrical

Ampere Ratings: /10 /10 /2 3 /4 8 /10
2 4 1

1 11/2 16/10 18/10

2 3 4 5

6 7 8 10

Approvals: Standard 248-14 UL Listed 1/2-5 Amps (File No: E10480) CSA Certified 1/2 ­ 5 Amps (File No: LR29862) Dimensions: 13/32" x 1-3/8"
Example part number (series & amperage): BLS 10

FLA Fuses
TIME-DELAY s 125 VAC
FLA fuses are 125 volt, pin-indicating timedelay fuses for protection of control circuit transformers, solenoids, and other circuits with high inrush currents. Metal indicating pin "pops-out" when fuse opens. Pin gives visual indication of open fuse. Use FLA fuses in conjunction with special fuseblocks to operate mechanical signal switches or energize alarm circuits. Fuses rated 12 amperes and above have dual-tube construction. Voltage Rating: 125 Volts AC Interrupting Rating: 10,000 amperes rms symmetrical

Ampere Ratings: /10 /100 2 /10 1 /4 3 /10 4 /10 1 /2 6 /10 8 /10 1 Approvals:
1 15

11/8 11/4 14/10 11/2 16/10 18/10 2 21/4 21/2

28/10 3 32/10 31/2 4 41/2 5 56/10 6

61/4 7 8 10 12 * 15 * 20 * 25 * 30 *

Standard 248-14 UL Listed (File No: E10480) CSA Certification Pending Dimensions: 13/32" x 1-1/2" * Note: Dual tube construction

Example part number (series & amperage): FLA 15

RECOMMENDED FUSE BLOCKS
L60030M series. Refer to Fuse Block section of this catalog for additional information.

50

Midget Fuses
Supplementary Overcurrent Protection

NEW

SPECIFICATIONS
Voltage Rating: 600VAC Interrupting Rating: 10,000 amperes Ampere Range: 1 ­ 6 amperes Approvals: Standard 248-14 UL Listed (File No: E10480) Dimensions: 13/32" x 1-3/8"

AMPERE RATINGS
1 1-6/10 2 3 4 5 6

RECOMMENDED FUSE BLOCKS
L60030M Series. Refer to Fuse Block section of this catalog for additional information.

ORDERING INFORMATION
Example catalog number: KLQ005 Example system number: 0KLQ005.T

CROSS REFERENCE
Littelfuse Buss KTQ Ferraz-Shawmut ­

KLQ Series Fuses
The Littelfuse KLQ series is designed to protect gaseous vapor fixtures, HID ballasts, and other electronic and lighting circuits. The KLQ is the same physical size as the Littelfuse BLS, but has more time delay to handle transient and inrush currents.

KLQ

NEW

SPECIFICATIONS
Voltage Rating: 1000 VAC/VDC Interrupting Rating: 44/100A: 10kA 11A: 20kA Ampere Range: 44/100 and 11 amperes Approvals: UL Recognized under the components program. (File No: E10480) CSA Certified (File No: LR29862) Dimensions: 44/100A: 13/32" x 1-3/8" 11A: 13/32" x 1-1/2"

ORDERING INFORMATION
Example catalog number: FLU011 Example system number: 0FLU011.T

CROSS REFERENCE
Littelfuse FLU Buss DMM Ferraz-Shawmut ­

FLU Series Fuses
The Littelfuse FLU series is designed specifically for the protection of multimeters. The 1000 VAC/VDC rating also makes the FLU ideal for a variety of other applications.

51

52
TIME IN SECONDS
200 400 300 10 8 6 40 30 .2 4 3 1000 800 600 .02 2 .4 .3 100 80 60 .04 .03 .1 .08 .06 .01 20 1 .8 .6 200 400 300 100 80 60 20 40 30 2 4 3 1000 800 600 10 8 6

TIME IN SECONDS

.2

.4 .3

1 .8 .6

.02

.04 .03

.1 .08 .06

FLM

KLK

.1 1/10A 15/100A .2 1/4A .3 .4 .6 .8 1 2 3 4 6 8 10 20 30 40 60 80 100 200 300 400 600 800 1000 1/2A 1A 1 1/2A 2A 2/10A 1/4A 3/10A 1/2A 1/8A .1

.2

.3 .4

.6 .8 1

Midget Fuses

2

3 4

6 8 10 8A 10A 15A 20A 25A 30A

CURRENT IN AMPERES

Supplementary Overcurrent Protection

CURRENT IN AMPERES
1000 800 600

20

30 40

60 80 100

200

300 400

600 800 1000

1 .1 .2 .3 .4 .6 .8 1 2 3 4 6 8 10 20 30 40 60 80 100 200 300 400 600 800 1000

2

3 4

6 8 10

20

30 40

60 80 100

CURRENT IN AMPERES

CURRENT IN AMPERES

200

300 400

600 800 1000

2000

3000 4000

6000 8000 10000

.01 3/4A 1A 1 1/2A 2A 2 1/2A 3A 3 1/2A 4A 5A 6A 7A 8A 9A 10A 12A 15A 20A 25A 30A

TIME IN SECONDS
200 400 300 100 80 60 20 10 8 6 40 30 4 3 2 .02 .01 .04 .03

TIME IN SECONDS
2 4 3 .2 .4 .3 1 .8 .6 100 80 60 200 400 300 .1 .08 .06 10 8 6 40 30 20

.04 .03

.1 .08 .06

.2

.4 .3

1 .8 .6

.02 8A 9A 10A 12A 14A 15A 20A 25A 30A

FLQ

KLKD

.01

1000 800 600 1/8A 2/10A 1/4A 3/10A 1/2A 3/4A 1A 1 1/2A 2A 2 1/2A 3A 3 1/2A 4A 5A 6A 7A 8A 9A 10A 12A 15A 20A 25A 30A